Symmetra RM Runtime Chart with
Standalone Extended Battery Cabinets

Units Load (in kVA/kW) Std. Runtime w/ incl. Battery modules Addl SKU's required for longer runtimes
  Runtime in minutes
10 15 20 30 45 60 90 120 180 240
SYH2K6RMT
SYH2K6RMI
SYH2K6RMT-P1
1/0.7 27 None None None 1a 1a 1a 2a 2a 4a 5a*
2/1.4 10 None 1a 1a 2a 2a 3a 4a 4a+ 1b+ 2d 4a+ 1b+ 3d 4a+ 1c+ 5d
SYH4K6RMT
SYH4K6RMI
SYH4K6RMT-P1
2/1.4 26 None None None 1a 1a 2a 3a* 2a+ 1b+ 2d 2a+ 1b+ 3d 2a+ 1c+ 6d
3/2.1 15 None None 1a 2a 3a* 2a+ 1b+ 2d 2a+ 1b+ 3d 2a+ 1b+ 3d 2a+ 1c+ 7d 2a+ 1c+ 9d
4/2.8 10 None 1a 2a 2a 2a+ 1b+ 2d 2a+ 1b+ 2d 2a+ 1c+ 5d 2a+ 1c+ 6d 2a+ 1c+ 10d 2a+ 2c+ 13d
SYH6K6RMT
SYH6K6RMI
SYH6K6RMT-P1
4/2.8 18 None None 1a* 1a* 1b+ 2d 1b+ 3d 1c+ 5d 1c+ 7d 1c+ 10d 2c+ 14d
5/3.5 13 None 1a* 1a* 1b+ 2d 1b+ 3d 1c+ 5d 1c+ 7d 1c+ 9d 2c+ 13d 2c+ 17d
6/4.2 11 None 1a 1b+ 2d 1b+ 2d 1c+ 5d 1c+ 5d 1c+ 8d 1c+ 11d 2c+ 16d 2c+ 20d
SYP8K12RMT
SYP8K12RMI
SYP8K12RMT-P1
4/2.8 14 None 1e 1e 2e 2e 2e+ 1b+ 1d 2e+ 1b+ 3d 2e+ 1c+ 5d 2e+ 1c+ 8d 2e+ 1c+ 12d
5/3.5 10 None 1e 1e 2e 2e+ 1b+ 1d 2e+ 1b+ 2d 2e+ 1c+ 5d 2e+ 1c+ 7d 2e+ 1c+ 11d 2e+ 2c+ 15d
6/4.2 7 1e 1e 1e 2e+ 1b+ 1d 2e+ 1b+ 2d 2e+ 1b+ 4d 2e+ 1c+ 6d 2e+ 1c+ 9d 2e+ 2c+ 14d 2e+ 2c+ 19d
7/4.9 6 1e 2e 2e+ 1b+ 1d 2e+ 1b+ 2d 2e+ 1b+ 3d 2e+ 1c+ 5d 2e+ 1c+ 8d 2e+ 1c+ 11d 2e+ 2c+ 17d 2e+ 2c+ 23d
8/5.6 6 1e 2e 2e+ 1b+ 1d 2e+ 1b+ 2d 2e+ 1b+ 4d 2e+ 1c+ 6d 2e+ 1c+ 9d 2e+ 2c+ 13d 2e+ 2c+ 20d 2e+ 3c+ 26d
SYP12K12RMT
SYP12K12RMI
SYP12K12RMT-P1
SYP12K12RMT-P2
7/4.9 11 None 1e 1e+ 1b+ 1d 1e+ 1b+ 2d 1e+ 1b+ 3d 1e+ 1c+ 5d 1e+ 1c+ 8d 1e+ 1c+ 11d 1e+ 2c+ 17d 1e+ 2c+ 23d
8/5.6 9 1e 1e 1e+ 1b+ 1d 1e+ 1b+ 2d 1e+ 1b+ 4d 1e+ 1c+ 6d 1e+ 1c+ 9d 1e+ 2c+ 13d 1e+ 2c+ 20d 1e+ 3c+ 26d
9/6.3 7 1e 1e+ 1b+ 1d 1e+ 1b+ 2d 1e+ 1b+ 4d 1e+ 1c+ 6d 1e+ 1c+ 8d 1e+ 2c+ 13d 1e+ 2c+ 18d 1e+ 3c+ 26d 1e+ 3c+ 34d
10/7.0 7 1e 1e+ 1b+ 1d 1e+ 1b+ 2d 1e+ 1b+ 4d 1e+ 1c+ 7d 1e+ 1c+ 10d 1e+ 2c+ 15d 1e+ 2c+ 20d 1e+ 3c+ 31d 1e+ 4c+ 39d
12/8.4 6 1e+ 1b+ 1d 1e+ 1b+ 2d 1e+ 1b+ 3d 1e+ 1c+ 6d 1e+ 1c+ 10d 1e+ 2c+ 13d 1e+ 2c+ 19d 1e+ 2c+ 24d 1e+ 3c+ 36d 1e+ 4c+ 48d
a = SYBT2
b = SYXR4-BM for 208/240V regions
b = SYXR4I-BM for 220/230/240V regions
c = SYXR12-BM for 208/240V regions
c = SYXR12I-BM for 220/230/240V regions
d = SYBATT
e = SYBT3
* If N+1 redundancy has been chosen in Step 2, then please add 1b to the configuration mentioned.